Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 625–648 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 114-4N24 cooling tower (944 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 114-4N24 — an AT cooling tower, 944 nominal tons (4149 kW): rated to cool 2841 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3112–5186 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-10KN-2 cooling tower (749 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-10KN-2 — a Series 1500 cooling tower, 749 nominal tons (3295 kW): rated to cool 2256 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2471–4118 kW | EU | Open in the builder |
| EVAPCO ATWB 12-7M28 closed-circuit cooler (849 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-7M28 — an ATWB closed-circuit cooler, 849 nominal tons (3732 kW): rated to cool 2130 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 83.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2799–4665 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-06M-2 cooling tower (874 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-06M-2 — a Series 3000 cooling tower, 874 nominal tons (3842 kW): rated to cool 2631 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2882–4803 kW | EU | Open in the builder |
| EVAPCO AT 114-4O24 cooling tower (995 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 114-4O24 — an AT cooling tower, 995 nominal tons (4373 kW): rated to cool 2994 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 97.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3279–5466 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT0-57-K cooling tower (57 tons, 250 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT0-57-K — a Series V cooling tower, 57 nominal tons (250 kW): rated to cool 171 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 6.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 187–312 kW | EU | Open in the builder |
| EVAPCO ATWB 12-7M36 closed-circuit cooler (996 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-7M36 — an ATWB closed-circuit cooler, 996 nominal tons (4379 kW): rated to cool 2499 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 103.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3284–5474 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-018-42H closed-circuit cooler (21 tons, 92 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-018-42H — a Series V closed circuit closed-circuit cooler, 21 nominal tons (92 kW): rated to cool 63 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 69–115 kW | EU | Open in the builder |
| EVAPCO AT 114-4P24 cooling tower (1052 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 114-4P24 — an AT cooling tower, 1052 nominal tons (4627 kW): rated to cool 3168 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 103.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3470–5783 kW | EU | Open in the builder |
| Baltimore Aircoil VCL-120 evaporative condenser (517 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-120 — a Series V EC evaporative condenser rejecting 517 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 10.5 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 388–646 kW | EU | Open in the builder |
| EVAPCO ATWB 12-7N14 closed-circuit cooler (465 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-7N14 — an ATWB closed-circuit cooler, 465 nominal tons (2044 kW): rated to cool 1166 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 45.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1533–2555 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1204A evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1204A — a VCA evaporative condenser rejecting 5187 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 80.3 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3890–6484 kW | EU | Open in the builder |
| EVAPCO AT 114-4Q24 cooling tower (1131 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 114-4Q24 — an AT cooling tower, 1131 nominal tons (4973 kW): rated to cool 3405 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 110.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3730–6216 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0301B-1012N-HB evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0301B-1012N-HB — a Vertex VRC evaporative condenser rejecting 1824 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 35.6 m³/s of the maker's own printed air, with a 19.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1368–2280 kW | EU | Open in the builder |
| EVAPCO ATWB 12-7N20 closed-circuit cooler (584 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-7N20 — an ATWB closed-circuit cooler, 584 nominal tons (2568 kW): rated to cool 1465 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 60.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1926–3210 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-1287-1236-120 evaporative condenser (7.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-1287-1236-120 — a CXVB evaporative condenser rejecting 7797 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 154.3 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5848–9746 kW | EU | Open in the builder |
| EVAPCO AT 114-5K26 cooling tower (1000 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 114-5K26 — an AT cooling tower, 1000 nominal tons (4395 kW): rated to cool 3009 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 94.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3296–5493 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-1774-2424-120 evaporative condenser (10.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-1774-2424-120 — a CXVT evaporative condenser rejecting 10776 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 191.9 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 8082–13470 kW | EU | Open in the builder |
| EVAPCO ATWB 12-7N28 closed-circuit cooler (930 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-7N28 — an ATWB closed-circuit cooler, 930 nominal tons (4088 kW): rated to cool 2333 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 90.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3066–5110 kW | EU | Open in the builder |
| Baltimore Aircoil FXT-0712C-J cooling tower (196 tons, 863 kW) — modelled Example modelled from published data BAC's FXT-0712C-J — an FXT cooling tower, 196 nominal tons (863 kW): rated to cool 591 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 647–1079 kW | EU | Open in the builder |
| EVAPCO AT 114-5L26 cooling tower (1074 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 114-5L26 — an AT cooling tower, 1074 nominal tons (4723 kW): rated to cool 3234 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 101.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3542–5904 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0809B-20D-M closed-circuit cooler (109 tons, 478 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0809B-20D-M — an FXV closed-circuit cooler, 109 nominal tons (478 kW): rated to cool 327 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 358–597 kW | EU | Open in the builder |
| EVAPCO ATWB 12-7N36 closed-circuit cooler (1091 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-7N36 — an ATWB closed-circuit cooler, 1091 nominal tons (4795 kW): rated to cool 2736 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 111.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3596–5994 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0166-0709N020 evaporative condenser (1.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0166-0709N020 — a PCC evaporative condenser rejecting 1008 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 23.9 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 756–1261 kW | EU | Open in the builder |