Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 577–600 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 114-2M24 cooling tower (720 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-2M24 — an AT cooling tower, 720 nominal tons (3163 kW): rated to cool 2166 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2373–3954 kWEUOpen in the builder
Baltimore Aircoil VCL-102 evaporative condenser (439 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-102 — a Series V EC evaporative condenser rejecting 439 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 11.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection329–549 kWEUOpen in the builder
EVAPCO ATWB 12-6N28 closed-circuit cooler (840 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6N28 — an ATWB closed-circuit cooler, 840 nominal tons (3694 kW): rated to cool 2108 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 93.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2771–4618 kWEUOpen in the builder
Baltimore Aircoil VCA-1170A evaporative condenser (5.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1170A — a VCA evaporative condenser rejecting 5041 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 72.7 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3780–6301 kWEUOpen in the builder
EVAPCO AT 114-2N24 cooling tower (778 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-2N24 — an AT cooling tower, 778 nominal tons (3422 kW): rated to cool 2343 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 94.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2566–4277 kWEUOpen in the builder
Baltimore Aircoil VRC-0297B-1012N-JB evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0297B-1012N-JB — a Vertex VRC evaporative condenser rejecting 1804 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 45.7 m³/s of the maker's own printed air, with a 30.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1353–2255 kWEUOpen in the builder
EVAPCO ATWB 12-6N36 closed-circuit cooler (1004 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6N36 — an ATWB closed-circuit cooler, 1004 nominal tons (4412 kW): rated to cool 2517 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 115.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3309–5515 kWEUOpen in the builder
Baltimore Aircoil CXVB-1257-1236-120 evaporative condenser (7.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-1257-1236-120 — a CXVB evaporative condenser rejecting 7615 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 156.0 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection5712–9519 kWEUOpen in the builder
EVAPCO AT 114-2O24 cooling tower (836 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-2O24 — an AT cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2757–4595 kWEUOpen in the builder
Baltimore Aircoil CXVT-1686-2424-120 evaporative condenser (10.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1686-2424-120 — a CXVT evaporative condenser rejecting 10241 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 196.2 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7681–12802 kWEUOpen in the builder
EVAPCO ATWB 12-6N40 closed-circuit cooler (1075 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6N40 — an ATWB closed-circuit cooler, 1075 nominal tons (4724 kW): rated to cool 2695 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 124.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3543–5905 kWEUOpen in the builder
Baltimore Aircoil FXT-0712B-K cooling tower (174 tons, 767 kW) — modelled Example modelled from published data
BAC's FXT-0712B-K — an FXT cooling tower, 174 nominal tons (767 kW): rated to cool 525 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection575–958 kWEUOpen in the builder
EVAPCO AT 114-3K24 cooling tower (706 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-3K24 — an AT cooling tower, 706 nominal tons (3102 kW): rated to cool 2124 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2327–3878 kWEUOpen in the builder
Baltimore Aircoil FXV-0809A-24T-L closed-circuit cooler (97 tons, 425 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0809A-24T-L — an FXV closed-circuit cooler, 97 nominal tons (425 kW): rated to cool 291 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 21.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection319–531 kWEUOpen in the builder
EVAPCO ATWB 12-6O20 closed-circuit cooler (581 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6O20 — an ATWB closed-circuit cooler, 581 nominal tons (2552 kW): rated to cool 1456 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 66.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1914–3190 kWEUOpen in the builder
Baltimore Aircoil PCC-0154-0709N015 evaporative condenser (935 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0154-0709N015 — a PCC evaporative condenser rejecting 935 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 19.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection702–1169 kWEUOpen in the builder
EVAPCO AT 114-3L24 cooling tower (772 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-3L24 — an AT cooling tower, 772 nominal tons (3396 kW): rated to cool 2325 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2547–4244 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-4D1EZ-G2 closed-circuit cooler (54 tons, 237 kW) — modelled Example modelled from published data
BAC's PFI-0412N-4D1EZ-G2 — a PFi closed-circuit cooler, 54 nominal tons (237 kW): rated to cool 162 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection177–296 kWEUOpen in the builder
EVAPCO ATWB 12-6O36 closed-circuit cooler (1077 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6O36 — an ATWB closed-circuit cooler, 1077 nominal tons (4735 kW): rated to cool 2702 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 123.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3552–5919 kWEUOpen in the builder
Baltimore Aircoil PT2-0812A-1M cooling tower (273 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0812A-1M — a PT2 cooling tower, 273 nominal tons (1200 kW): rated to cool 822 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection900–1501 kWEUOpen in the builder
EVAPCO AT 114-3M24 cooling tower (809 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-3M24 — an AT cooling tower, 809 nominal tons (3558 kW): rated to cool 2436 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2668–4447 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-10KN cooling tower (375 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-10KN — a Series 1500 cooling tower, 375 nominal tons (1647 kW): rated to cool 1128 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1236–2059 kWEUOpen in the builder
EVAPCO ATWB 12-6O40 closed-circuit cooler (1153 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6O40 — an ATWB closed-circuit cooler, 1153 nominal tons (5070 kW): rated to cool 2893 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 132.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3802–6337 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-06M cooling tower (437 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-06M — a Series 3000 cooling tower, 437 nominal tons (1919 kW): rated to cool 1314 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1439–2399 kWEUOpen in the builder
‹ Previous1…2324252627…145Next ›