Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 529–552 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 112-4M18 cooling tower (640 tons, 2.8 MW) — modelled Example modelled from published data
EVAPCO's 112-4M18 — an AT cooling tower, 640 nominal tons (2813 kW): rated to cool 1926 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2110–3516 kWEUOpen in the builder
Baltimore Aircoil CXVT-1614-2826-80 evaporative condenser (9.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1614-2826-80 — a CXVT evaporative condenser rejecting 9804 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 187.2 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7353–12255 kWEUOpen in the builder
EVAPCO ATWB 12-5O20 closed-circuit cooler (542 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-5O20 — an ATWB closed-circuit cooler, 542 nominal tons (2383 kW): rated to cool 1360 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 68.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1787–2978 kWEUOpen in the builder
Baltimore Aircoil FXT-0712B-H cooling tower (140 tons, 613 kW) — modelled Example modelled from published data
BAC's FXT-0712B-H — an FXT cooling tower, 140 nominal tons (613 kW): rated to cool 420 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 19.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection460–767 kWEUOpen in the builder
EVAPCO AT 112-4M20 cooling tower (653 tons, 2.9 MW) — modelled Example modelled from published data
EVAPCO's 112-4M20 — an AT cooling tower, 653 nominal tons (2870 kW): rated to cool 1965 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2152–3587 kWEUOpen in the builder
Baltimore Aircoil FXV-0809A-16D-L closed-circuit cooler (83 tons, 364 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0809A-16D-L — an FXV closed-circuit cooler, 83 nominal tons (364 kW): rated to cool 249 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 22.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection273–455 kWEUOpen in the builder
EVAPCO ATWB 12-5O36 closed-circuit cooler (999 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-5O36 — an ATWB closed-circuit cooler, 999 nominal tons (4393 kW): rated to cool 2506 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 127.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3294–5491 kWEUOpen in the builder
Baltimore Aircoil PCC-0134-0412N015 evaporative condenser (814 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0134-0412N015 — a PCC evaporative condenser rejecting 814 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 14.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection610–1017 kWEUOpen in the builder
EVAPCO AT 112-4N12 cooling tower (513 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-4N12 — an AT cooling tower, 513 nominal tons (2256 kW): rated to cool 1545 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1692–2821 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-3D2EZ-G2 closed-circuit cooler (48 tons, 210 kW) — modelled Example modelled from published data
BAC's PFI-0412N-3D2EZ-G2 — a PFi closed-circuit cooler, 48 nominal tons (210 kW): rated to cool 144 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection158–263 kWEUOpen in the builder
EVAPCO ATWB 12-5O40 closed-circuit cooler (1077 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-5O40 — an ATWB closed-circuit cooler, 1077 nominal tons (4733 kW): rated to cool 2700 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 137.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3549–5916 kWEUOpen in the builder
Baltimore Aircoil PT2-0809A-4M cooling tower (263 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0809A-4M — a PT2 cooling tower, 263 nominal tons (1157 kW): rated to cool 792 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection868–1446 kWEUOpen in the builder
EVAPCO AT 112-4N14 cooling tower (572 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-4N14 — an AT cooling tower, 572 nominal tons (2515 kW): rated to cool 1722 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1886–3144 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-09LN cooling tower (400 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-09LN — a Series 1500 cooling tower, 400 nominal tons (1757 kW): rated to cool 1203 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1318–2196 kWEUOpen in the builder
EVAPCO ATWB 12-5P20 closed-circuit cooler (574 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-5P20 — an ATWB closed-circuit cooler, 574 nominal tons (2525 kW): rated to cool 1441 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 72.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1894–3156 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1020-07P cooling tower (528 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1020-07P — a Series 3000 cooling tower, 528 nominal tons (2322 kW): rated to cool 1590 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1742–2903 kWEUOpen in the builder
EVAPCO AT 112-4N18 cooling tower (703 tons, 3.1 MW) — modelled Example modelled from published data
EVAPCO's 112-4N18 — an AT cooling tower, 703 nominal tons (3089 kW): rated to cool 2115 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2317–3861 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-32-H cooling tower (32 tons, 140 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-32-H — a Series V cooling tower, 32 nominal tons (140 kW): rated to cool 96 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 5.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection105–175 kWEUOpen in the builder
EVAPCO ATWB 12-5P40 closed-circuit cooler (1141 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-5P40 — an ATWB closed-circuit cooler, 1141 nominal tons (5015 kW): rated to cool 2862 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 144.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3762–6269 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-018-32G closed-circuit cooler (16 tons, 70 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-018-32G — a Series V closed circuit closed-circuit cooler, 16 nominal tons (70 kW): rated to cool 48 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 4.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection53–88 kWEUOpen in the builder
EVAPCO AT 112-4N20 cooling tower (726 tons, 3.2 MW) — modelled Example modelled from published data
EVAPCO's 112-4N20 — an AT cooling tower, 726 nominal tons (3190 kW): rated to cool 2184 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2392–3987 kWEUOpen in the builder
Baltimore Aircoil VCL-096 evaporative condenser (414 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-096 — a Series V EC evaporative condenser rejecting 414 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 10.2 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection310–517 kWEUOpen in the builder
EVAPCO ATWB 12-6L14 closed-circuit cooler (361 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6L14 — an ATWB closed-circuit cooler, 361 nominal tons (1587 kW): rated to cool 905 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 40.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1190–1983 kWEUOpen in the builder
Baltimore Aircoil VCA-1169A evaporative condenser (5.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1169A — a VCA evaporative condenser rejecting 5041 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 88.3 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3780–6301 kWEUOpen in the builder
‹ Previous1…2122232425…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers