Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 3,265–3,288 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
Baltimore Aircoil PCC-1501-2436N060 evaporative condenser (9.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1501-2436N060 — a PCC evaporative condenser rejecting 9120 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 196.8 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection6840–11400 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-4D4DS-O1 closed-circuit cooler (264 tons, 1.2 MW) — modelled Example modelled from published data
BAC's PFI-1218N-4D4DS-O1 — a PFi closed-circuit cooler, 264 nominal tons (1161 kW): rated to cool 795 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 54.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection871–1451 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-8518-07G cooling tower (215 tons, 946 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-8518-07G — a Series 3000 cooling tower, 215 nominal tons (946 kW): rated to cool 648 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection710–1183 kWEUOpen in the builder
Baltimore Aircoil PCC-1580-2424N160 evaporative condenser (9.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1580-2424N160 — a PCC evaporative condenser rejecting 9597 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 166.1 m³/s of the maker's own printed air, with a 119.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7198–11997 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-4D4DS-P1 closed-circuit cooler (285 tons, 1.3 MW) — modelled Example modelled from published data
BAC's PFI-1218N-4D4DS-P1 — a PFi closed-circuit cooler, 285 nominal tons (1253 kW): rated to cool 858 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 59.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection940–1566 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-8518-07H cooling tower (255 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-8518-07H — a Series 3000 cooling tower, 255 nominal tons (1122 kW): rated to cool 768 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection841–1402 kWEUOpen in the builder
Baltimore Aircoil PCC-1584-2424N160 evaporative condenser (9.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1584-2424N160 — a PCC evaporative condenser rejecting 9622 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 167.5 m³/s of the maker's own printed air, with a 119.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7216–12027 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-4D4ES-Q1 closed-circuit cooler (318 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-1218N-4D4ES-Q1 — a PFi closed-circuit cooler, 318 nominal tons (1398 kW): rated to cool 957 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1048–1747 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-8518-07J cooling tower (291 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-8518-07J — a Series 3000 cooling tower, 291 nominal tons (1279 kW): rated to cool 876 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection960–1599 kWEUOpen in the builder
Baltimore Aircoil PCC-1624-2424N160 evaporative condenser (9.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1624-2424N160 — a PCC evaporative condenser rejecting 9865 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 159.5 m³/s of the maker's own printed air, with a 119.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7399–12331 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-4D4ES-R1 closed-circuit cooler (333 tons, 1.5 MW) — modelled Example modelled from published data
BAC's PFI-1218N-4D4ES-R1 — a PFi closed-circuit cooler, 333 nominal tons (1463 kW): rated to cool 1002 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 65.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1098–1829 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-8518-07K cooling tower (319 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-8518-07K — a Series 3000 cooling tower, 319 nominal tons (1402 kW): rated to cool 960 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1052–1753 kWEUOpen in the builder
Baltimore Aircoil PCC-1710-2440N060 evaporative condenser (10.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1710-2440N060 — a PCC evaporative condenser rejecting 10389 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 209.2 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7792–12986 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-5D2ES-Q1 closed-circuit cooler (329 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-1218N-5D2ES-Q1 — a PFi closed-circuit cooler, 329 nominal tons (1446 kW): rated to cool 990 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 63.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1084–1807 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-8518-07L cooling tower (364 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-8518-07L — a Series 3000 cooling tower, 364 nominal tons (1599 kW): rated to cool 1095 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1199–1999 kWEUOpen in the builder
Baltimore Aircoil PCC-1738-2436N080 evaporative condenser (10.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1738-2436N080 — a PCC evaporative condenser rejecting 10556 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 196.7 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7917–13195 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-6D1ES-R1 closed-circuit cooler (359 tons, 1.6 MW) — modelled Example modelled from published data
BAC's PFI-1218N-6D1ES-R1 — a PFi closed-circuit cooler, 359 nominal tons (1577 kW): rated to cool 1080 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1183–1972 kWEUOpen in the builder
Baltimore Aircoil PCC-1848-2436N080 evaporative condenser (11.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1848-2436N080 — a PCC evaporative condenser rejecting 11226 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 183.8 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection8420–14033 kWEUOpen in the builder
Baltimore Aircoil PFI-1218N-6D3ES-R1 closed-circuit cooler (351 tons, 1.5 MW) — modelled Example modelled from published data
BAC's PFI-1218N-6D3ES-R1 — a PFi closed-circuit cooler, 351 nominal tons (1542 kW): rated to cool 1056 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1157–1928 kWEUOpen in the builder
Baltimore Aircoil PCC-1947-2436N160 evaporative condenser (11.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1947-2436N160 — a PCC evaporative condenser rejecting 11825 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 259.7 m³/s of the maker's own printed air, with a 119.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection8869–14781 kWEUOpen in the builder
Baltimore Aircoil PFI-1224N-2D4DS-K2 closed-circuit cooler (198 tons, 872 kW) — modelled Example modelled from published data
BAC's PFI-1224N-2D4DS-K2 — a PFi closed-circuit cooler, 198 nominal tons (872 kW): rated to cool 597 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 65.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection654–1090 kWEUOpen in the builder
Baltimore Aircoil PCC-1948-2440N080 evaporative condenser (11.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1948-2440N080 — a PCC evaporative condenser rejecting 11835 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 208.1 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection8876–14794 kWEUOpen in the builder
Baltimore Aircoil PFI-1224N-2D4ES-M2 closed-circuit cooler (238 tons, 1.0 MW) — modelled Example modelled from published data
BAC's PFI-1224N-2D4ES-M2 — a PFi closed-circuit cooler, 238 nominal tons (1047 kW): rated to cool 717 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 78.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection785–1309 kWEUOpen in the builder
Baltimore Aircoil PCC-2037-2436N120 evaporative condenser (12.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-2037-2436N120 — a PCC evaporative condenser rejecting 12375 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 207.7 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection9281–15469 kWEUOpen in the builder
‹ Previous1…135136137138139…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers