EVAPCO AT 19-2J12 cooling tower (256 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-2J12 — an AT cooling tower, 256 nominal tons (1126 kW): rated to cool 771 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection845–1408 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-4D3ES-J1 closed-circuit cooler (70 tons, 307 kW) — modelled Example modelled from published data
BAC's PFI-0709N-4D3ES-J1 — a PFi closed-circuit cooler, 70 nominal tons (307 kW): rated to cool 210 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 14.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection230–383 kWEUOpen in the builder
EVAPCO ATWB 24-3L14 closed-circuit cooler (559 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3L14 — an ATWB closed-circuit cooler, 559 nominal tons (2456 kW): rated to cool 1402 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 89.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1842–3070 kWEUOpen in the builder
Baltimore Aircoil PT2-1012A-3P cooling tower (424 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1012A-3P — a PT2 cooling tower, 424 nominal tons (1862 kW): rated to cool 1275 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1397–2328 kWEUOpen in the builder
EVAPCO AT 19-2J14 cooling tower (279 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-2J14 — an AT cooling tower, 279 nominal tons (1227 kW): rated to cool 840 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection920–1533 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-12KN-2 cooling tower (799 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-12KN-2 — a Series 1500 cooling tower, 799 nominal tons (3514 kW): rated to cool 2406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2635–4392 kWEUOpen in the builder
EVAPCO ATWB 24-3L20 closed-circuit cooler (762 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3L20 — an ATWB closed-circuit cooler, 762 nominal tons (3349 kW): rated to cool 1911 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 117.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2512–4186 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-10P-2 cooling tower (1509 tons, 6.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-10P-2 — a Series 3000 cooling tower, 1509 nominal tons (6633 kW): rated to cool 4542 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 170.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4975–8292 kWEUOpen in the builder
EVAPCO AT 19-2J9 cooling tower (207 tons, 911 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-2J9 — an AT cooling tower, 207 nominal tons (911 kW): rated to cool 624 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection683–1139 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-416-O cooling tower (415 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-416-O — a Series V cooling tower, 415 nominal tons (1823 kW): rated to cool 1248 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1367–2278 kWEUOpen in the builder
EVAPCO ATWB 24-3L28 closed-circuit cooler (1067 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3L28 — an ATWB closed-circuit cooler, 1067 nominal tons (4692 kW): rated to cool 2677 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 179.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3519–5865 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-036-32J closed-circuit cooler (37 tons, 162 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-036-32J — a Series V closed circuit closed-circuit cooler, 37 nominal tons (162 kW): rated to cool 111 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 9.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection122–203 kWEUOpen in the builder
EVAPCO AT 19-2K12 cooling tower (282 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-2K12 — an AT cooling tower, 282 nominal tons (1240 kW): rated to cool 849 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection930–1550 kWEUOpen in the builder
Baltimore Aircoil VCA-1558A evaporative condenser (6.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1558A — a VCA evaporative condenser rejecting 6712 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 101.8 m³/s of the maker's own printed air, with a 67.1 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection5034–8390 kWEUOpen in the builder
EVAPCO ATWB 24-3M12 closed-circuit cooler (514 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3M12 — an ATWB closed-circuit cooler, 514 nominal tons (2261 kW): rated to cool 1290 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 84.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1696–2826 kWEUOpen in the builder
Baltimore Aircoil VRC-0360B-1018N-JA evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0360B-1018N-JA — a Vertex VRC evaporative condenser rejecting 2184 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 47.4 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1638–2730 kWEUOpen in the builder
EVAPCO AT 19-2K14 cooling tower (308 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-2K14 — an AT cooling tower, 308 nominal tons (1354 kW): rated to cool 927 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1015–1692 kWEUOpen in the builder
Baltimore Aircoil CXVB-217-0812-15 evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-217-0812-15 — a CXVB evaporative condenser rejecting 1315 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 31.0 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection986–1643 kWEUOpen in the builder
EVAPCO ATWB 24-3M14 closed-circuit cooler (595 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3M14 — an ATWB closed-circuit cooler, 595 nominal tons (2615 kW): rated to cool 1492 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 94.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1961–3269 kWEUOpen in the builder
Baltimore Aircoil CXVT-807-1426-40 evaporative condenser (4.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-807-1426-40 — a CXVT evaporative condenser rejecting 4901 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 93.6 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3676–6126 kWEUOpen in the builder
EVAPCO AT 19-2L14 cooling tower (336 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-2L14 — an AT cooling tower, 336 nominal tons (1477 kW): rated to cool 1011 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1107–1846 kWEUOpen in the builder
Baltimore Aircoil FXV-0812B-16Q-O closed-circuit cooler (125 tons, 548 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812B-16Q-O — an FXV closed-circuit cooler, 125 nominal tons (548 kW): rated to cool 375 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 39.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection411–685 kWEUOpen in the builder
EVAPCO ATWB 24-3M18 closed-circuit cooler (748 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3M18 — an ATWB closed-circuit cooler, 748 nominal tons (3290 kW): rated to cool 1877 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 116.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2467–4112 kWEUOpen in the builder
Baltimore Aircoil PCC-0281-1012N025 evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0281-1012N025 — a PCC evaporative condenser rejecting 1707 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 35.3 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1280–2134 kWEUOpen in the builder