Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,057–1,080 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 19-3F6 cooling tower (101 tons, 443 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-3F6 — an AT cooling tower, 101 nominal tons (443 kW): rated to cool 303 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 10.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection332–553 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-4D4DS-J1 closed-circuit cooler (66 tons, 289 kW) — modelled Example modelled from published data
BAC's PFI-0709N-4D4DS-J1 — a PFi closed-circuit cooler, 66 nominal tons (289 kW): rated to cool 198 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 14.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection217–361 kWEUOpen in the builder
EVAPCO ATWB 24-3M20 closed-circuit cooler (810 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3M20 — an ATWB closed-circuit cooler, 810 nominal tons (3560 kW): rated to cool 2031 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 125.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2670–4450 kWEUOpen in the builder
Baltimore Aircoil PT2-1012A-4P cooling tower (432 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1012A-4P — a PT2 cooling tower, 432 nominal tons (1897 kW): rated to cool 1299 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1423–2371 kWEUOpen in the builder
EVAPCO AT 19-3F8 cooling tower (123 tons, 539 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-3F8 — an AT cooling tower, 123 nominal tons (539 kW): rated to cool 369 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection404–674 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-12LC cooling tower (428 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-12LC — a Series 1500 cooling tower, 428 nominal tons (1880 kW): rated to cool 1287 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1410–2350 kWEUOpen in the builder
EVAPCO ATWB 24-3N14 closed-circuit cooler (656 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3N14 — an ATWB closed-circuit cooler, 656 nominal tons (2883 kW): rated to cool 1645 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 102.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2162–3603 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-10Q cooling tower (807 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-10Q — a Series 3000 cooling tower, 807 nominal tons (3549 kW): rated to cool 2430 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2662–4436 kWEUOpen in the builder
EVAPCO AT 19-3G11 cooling tower (171 tons, 754 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-3G11 — an AT cooling tower, 171 nominal tons (754 kW): rated to cool 516 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection565–942 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-478-N cooling tower (476 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-478-N — a Series V cooling tower, 476 nominal tons (2094 kW): rated to cool 1434 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1571–2618 kWEUOpen in the builder
EVAPCO ATWB 24-3N18 closed-circuit cooler (823 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3N18 — an ATWB closed-circuit cooler, 823 nominal tons (3620 kW): rated to cool 2066 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 126.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2715–4525 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-036-41L closed-circuit cooler (47 tons, 206 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-036-41L — a Series V closed circuit closed-circuit cooler, 47 nominal tons (206 kW): rated to cool 141 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection154–257 kWEUOpen in the builder
EVAPCO AT 19-3G6 cooling tower (124 tons, 543 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-3G6 — an AT cooling tower, 124 nominal tons (543 kW): rated to cool 372 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection407–679 kWEUOpen in the builder
Baltimore Aircoil VCA-1570A evaporative condenser (6.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1570A — a VCA evaporative condenser rejecting 6764 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 115.8 m³/s of the maker's own printed air, with a 67.1 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection5073–8455 kWEUOpen in the builder
EVAPCO ATWB 24-3N20 closed-circuit cooler (891 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3N20 — an ATWB closed-circuit cooler, 891 nominal tons (3916 kW): rated to cool 2234 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 136.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2937–4895 kWEUOpen in the builder
Baltimore Aircoil VRC-0362B-1018N-HA evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0362B-1018N-HA — a Vertex VRC evaporative condenser rejecting 2197 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1648–2746 kWEUOpen in the builder
EVAPCO AT 19-3G8 cooling tower (151 tons, 666 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-3G8 — an AT cooling tower, 151 nominal tons (666 kW): rated to cool 456 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection499–832 kWEUOpen in the builder
Baltimore Aircoil CXVB-221-0812-7.5 evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-221-0812-7.5 — a CXVB evaporative condenser rejecting 1339 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 24.1 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1004–1674 kWEUOpen in the builder
EVAPCO ATWB 24-3O20 closed-circuit cooler (958 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-3O20 — an ATWB closed-circuit cooler, 958 nominal tons (4213 kW): rated to cool 2404 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 145.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3160–5266 kWEUOpen in the builder
Baltimore Aircoil CXVT-813-1224-50 evaporative condenser (4.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-813-1224-50 — a CXVT evaporative condenser rejecting 4936 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 92.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3702–6170 kWEUOpen in the builder
EVAPCO AT 19-3G9 cooling tower (153 tons, 675 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-3G9 — an AT cooling tower, 153 nominal tons (675 kW): rated to cool 462 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection506–843 kWEUOpen in the builder
Baltimore Aircoil FXV-0812B-20D-O closed-circuit cooler (162 tons, 714 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812B-20D-O — an FXV closed-circuit cooler, 162 nominal tons (714 kW): rated to cool 489 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 39.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection536–893 kWEUOpen in the builder
EVAPCO ATWB 24-4K12 closed-circuit cooler (487 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-4K12 — an ATWB closed-circuit cooler, 487 nominal tons (2139 kW): rated to cool 1221 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 73.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1604–2674 kWEUOpen in the builder
Baltimore Aircoil PCC-0293-1212N015 evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0293-1212N015 — a PCC evaporative condenser rejecting 1780 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.4 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1335–2225 kWEUOpen in the builder
‹ Previous1…4344454647…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers