Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,057–1,080 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 19-3F6 cooling tower (101 tons, 443 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3F6 — an AT cooling tower, 101 nominal tons (443 kW): rated to cool 303 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 10.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 332–553 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0709N-4D4DS-J1 closed-circuit cooler (66 tons, 289 kW) — modelled Example modelled from published data BAC's PFI-0709N-4D4DS-J1 — a PFi closed-circuit cooler, 66 nominal tons (289 kW): rated to cool 198 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 14.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 217–361 kW | EU | Open in the builder |
| EVAPCO ATWB 24-3M20 closed-circuit cooler (810 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-3M20 — an ATWB closed-circuit cooler, 810 nominal tons (3560 kW): rated to cool 2031 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 125.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2670–4450 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-1012A-4P cooling tower (432 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-1012A-4P — a PT2 cooling tower, 432 nominal tons (1897 kW): rated to cool 1299 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1423–2371 kW | EU | Open in the builder |
| EVAPCO AT 19-3F8 cooling tower (123 tons, 539 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3F8 — an AT cooling tower, 123 nominal tons (539 kW): rated to cool 369 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 404–674 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-12LC cooling tower (428 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-12LC — a Series 1500 cooling tower, 428 nominal tons (1880 kW): rated to cool 1287 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1410–2350 kW | EU | Open in the builder |
| EVAPCO ATWB 24-3N14 closed-circuit cooler (656 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-3N14 — an ATWB closed-circuit cooler, 656 nominal tons (2883 kW): rated to cool 1645 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 102.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2162–3603 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-10Q cooling tower (807 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-10Q — a Series 3000 cooling tower, 807 nominal tons (3549 kW): rated to cool 2430 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2662–4436 kW | EU | Open in the builder |
| EVAPCO AT 19-3G11 cooling tower (171 tons, 754 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3G11 — an AT cooling tower, 171 nominal tons (754 kW): rated to cool 516 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 565–942 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-478-N cooling tower (476 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-478-N — a Series V cooling tower, 476 nominal tons (2094 kW): rated to cool 1434 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1571–2618 kW | EU | Open in the builder |
| EVAPCO ATWB 24-3N18 closed-circuit cooler (823 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-3N18 — an ATWB closed-circuit cooler, 823 nominal tons (3620 kW): rated to cool 2066 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 126.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2715–4525 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-036-41L closed-circuit cooler (47 tons, 206 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-036-41L — a Series V closed circuit closed-circuit cooler, 47 nominal tons (206 kW): rated to cool 141 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 154–257 kW | EU | Open in the builder |
| EVAPCO AT 19-3G6 cooling tower (124 tons, 543 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3G6 — an AT cooling tower, 124 nominal tons (543 kW): rated to cool 372 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 407–679 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1570A evaporative condenser (6.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1570A — a VCA evaporative condenser rejecting 6764 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 115.8 m³/s of the maker's own printed air, with a 67.1 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5073–8455 kW | EU | Open in the builder |
| EVAPCO ATWB 24-3N20 closed-circuit cooler (891 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-3N20 — an ATWB closed-circuit cooler, 891 nominal tons (3916 kW): rated to cool 2234 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 136.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2937–4895 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0362B-1018N-HA evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0362B-1018N-HA — a Vertex VRC evaporative condenser rejecting 2197 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1648–2746 kW | EU | Open in the builder |
| EVAPCO AT 19-3G8 cooling tower (151 tons, 666 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3G8 — an AT cooling tower, 151 nominal tons (666 kW): rated to cool 456 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 499–832 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-221-0812-7.5 evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-221-0812-7.5 — a CXVB evaporative condenser rejecting 1339 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 24.1 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1004–1674 kW | EU | Open in the builder |
| EVAPCO ATWB 24-3O20 closed-circuit cooler (958 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-3O20 — an ATWB closed-circuit cooler, 958 nominal tons (4213 kW): rated to cool 2404 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 145.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3160–5266 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-813-1224-50 evaporative condenser (4.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-813-1224-50 — a CXVT evaporative condenser rejecting 4936 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 92.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3702–6170 kW | EU | Open in the builder |
| EVAPCO AT 19-3G9 cooling tower (153 tons, 675 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3G9 — an AT cooling tower, 153 nominal tons (675 kW): rated to cool 462 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 506–843 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0812B-20D-O closed-circuit cooler (162 tons, 714 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0812B-20D-O — an FXV closed-circuit cooler, 162 nominal tons (714 kW): rated to cool 489 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 39.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 536–893 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4K12 closed-circuit cooler (487 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4K12 — an ATWB closed-circuit cooler, 487 nominal tons (2139 kW): rated to cool 1221 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 73.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1604–2674 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0293-1212N015 evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0293-1212N015 — a PCC evaporative condenser rejecting 1780 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.4 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1335–2225 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers