Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,105–1,128 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 19-3I11 cooling tower (220 tons, 968 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3I11 — an AT cooling tower, 220 nominal tons (968 kW): rated to cool 663 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 726–1210 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0709N-5D2DS-M1 closed-circuit cooler (88 tons, 386 kW) — modelled Example modelled from published data BAC's PFI-0709N-5D2DS-M1 — a PFi closed-circuit cooler, 88 nominal tons (386 kW): rated to cool 264 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 20.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 289–482 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4L20 closed-circuit cooler (802 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4L20 — an ATWB closed-circuit cooler, 802 nominal tons (3527 kW): rated to cool 2012 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 114.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2645–4408 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-1212A-1O cooling tower (381 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-1212A-1O — a PT2 cooling tower, 381 nominal tons (1674 kW): rated to cool 1146 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1255–2092 kW | EU | Open in the builder |
| EVAPCO AT 19-3I12 cooling tower (255 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3I12 — an AT cooling tower, 255 nominal tons (1122 kW): rated to cool 768 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 841–1402 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-12LN cooling tower (448 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-12LN — a Series 1500 cooling tower, 448 nominal tons (1967 kW): rated to cool 1347 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1475–2459 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4L28 closed-circuit cooler (1149 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4L28 — an ATWB closed-circuit cooler, 1149 nominal tons (5051 kW): rated to cool 2882 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 174.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3788–6314 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-10R cooling tower (853 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-10R — a Series 3000 cooling tower, 853 nominal tons (3750 kW): rated to cool 2568 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2813–4688 kW | EU | Open in the builder |
| EVAPCO AT 19-3I14 cooling tower (279 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3I14 — an AT cooling tower, 279 nominal tons (1227 kW): rated to cool 840 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 920–1533 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-550-P cooling tower (548 tons, 2.4 MW) — modelled Example modelled from published data BAC's VT1-550-P — a Series V cooling tower, 548 nominal tons (2410 kW): rated to cool 1650 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1807–3012 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4M12 closed-circuit cooler (559 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4M12 — an ATWB closed-circuit cooler, 559 nominal tons (2458 kW): rated to cool 1403 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 82.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1844–3073 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-048-21L closed-circuit cooler (48 tons, 210 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-048-21L — a Series V closed circuit closed-circuit cooler, 48 nominal tons (210 kW): rated to cool 144 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 15.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 158–263 kW | EU | Open in the builder |
| EVAPCO AT 19-3I6 cooling tower (150 tons, 657 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3I6 — an AT cooling tower, 150 nominal tons (657 kW): rated to cool 450 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 15.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 493–822 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1654A evaporative condenser (7.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1654A — a VCA evaporative condenser rejecting 7126 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 115.3 m³/s of the maker's own printed air, with a 67.1 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5344–8907 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4M14 closed-circuit cooler (639 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4M14 — an ATWB closed-circuit cooler, 639 nominal tons (2810 kW): rated to cool 1603 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 91.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2107–3512 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0374B-1218N-HA evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0374B-1218N-HA — a Vertex VRC evaporative condenser rejecting 2266 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1700–2833 kW | EU | Open in the builder |
| EVAPCO AT 19-3I8 cooling tower (178 tons, 784 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3I8 — an AT cooling tower, 178 nominal tons (784 kW): rated to cool 537 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 588–980 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-237-0812-10 evaporative condenser (1.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-237-0812-10 — a CXVB evaporative condenser rejecting 1436 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 26.6 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1077–1795 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4M18 closed-circuit cooler (792 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4M18 — an ATWB closed-circuit cooler, 792 nominal tons (3480 kW): rated to cool 1986 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 113.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2610–4350 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-844-1426-50 evaporative condenser (5.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-844-1426-50 — a CXVT evaporative condenser rejecting 5124 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 100.8 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3843–6405 kW | EU | Open in the builder |
| EVAPCO AT 19-3I9 cooling tower (198 tons, 872 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 19-3I9 — an AT cooling tower, 198 nominal tons (872 kW): rated to cool 597 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 654–1090 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0812B-24D-L closed-circuit cooler (160 tons, 705 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0812B-24D-L — an FXV closed-circuit cooler, 160 nominal tons (705 kW): rated to cool 483 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 529–882 kW | EU | Open in the builder |
| EVAPCO ATWB 24-4M20 closed-circuit cooler (852 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-4M20 — an ATWB closed-circuit cooler, 852 nominal tons (3746 kW): rated to cool 2138 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 121.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2810–4683 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0300-0718N040 evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0300-0718N040 — a PCC evaporative condenser rejecting 1822 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 45.0 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1367–2278 kW | EU | Open in the builder |